Rockwell Automation 6180 RAC6180 Industrial Computers Installation Instructions User Manual

Page 14

Advertising
background image

14

RAC6180 Industrial Computers

Publication 6180-IN001B-EN-P

ATTENTION: Be careful not to damage the sealing
gasket when installing or removing studs. A damaged
seal may result in damage to the RAC6180 and other
panel components due to a leaking seal.

3. Make sure the sealing gasket is properly positioned on the terminal.

This gasket forms a compression type seal (NEMA Type 4x). Do not
use sealing compounds.

4. Place the RAC6180 in the panel cutout aligning the studs with the

mounting holes. The RAC6180 will snap into the panel as the
temporary retaining tabs lock against the panel (see note following).

Note:

Versions of the RAC6180 designed for panel mounting
have metal tabs that temporarily lock the RAC6180 against
the panel. These tabs only facilitate installation of the
mounting hardware. The tabs are not designed to provide
permanent mounting.

5. Install the 18 self–locking nuts hand tight.

ATTENTION: Tighten mounting nuts to a torque of 10
inch pounds (1.1 N•m) to provide a proper seal and
prevent damage to the RAC6180. Rockwell Automation
assumes no responsibility for water or chemical damage
to the terminal or other equipment within the enclosure
because of improper installation.