Install the Terminal

Before installing the terminal in a panel, review these topics:

Mounting clearances

Panel cutout dimensions

Product dimensions

Mounting Clearances

Allow adequate clearance around the terminal, inside the enclosure, for adequate ventilation.
Consider heat produced by other devices in the enclosure. The ambient temperature around
the terminals must be between 0…55 °C (32…131 °F).

Minimum clearances for ventilation are:

Top clearance: 51 mm (2 in.)

Bottom clearance: 102 mm (4 in.)

Side clearances: 25 mm (1 in.)

Back clearance: 0 mm (0 in.)

Minimum side clearance for insertion of memory card is 102 mm (4 in.).

Panel Cutout Dimensions

Use the full size template shipped with your terminal to mark the cutout dimensions.

Mount the Terminal in a Panel

Mounting levers secure the terminal to the panel. The number of levers you use

(4 or 6) varies by terminal type.

Terminal Type

Height, mm (in.)

Width, mm (in.)

400 Keypad or Keypad and Touch

123 (4.86)

156 (6.15)

600 Keypad or Keypad and Touch

142 (5.61)

241 (9.50)

600 Touch

123 (4.86)

156 (6.15)

ATTENTION

Disconnect all electrical power from the panel before making the panel cutout.

Make sure the area around the panel cutout is clear.

Take precautions so metal cuttings do not enter any components already installed in
the panel.

Failure to follow these instructions may result in personal injury or damage to panel
components.