Wiring and Safety Guidelines

Use publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces, IEC
60364 Electrical Installations in Buildings, or other applicable wiring safety requirements for
the country of installation when wiring the devices. In addition to the NFPA guidelines:

connect the device and other similar electronic equipment to its own branch circuit.

protect the input power by a fuse or circuit breaker rated at no more than 15 A.

route incoming power to the device by a separate path from the communication lines.

cross power and communication lines at right angles if they must cross.
Communication lines can be installed in the same conduit as low-level

DC I/O lines (less than 10V).

shield and ground cables appropriately to avoid electromagnetic interference (EMI).
Grounding minimizes noise from EMI and is a safety measure in electrical
installations.

For more information on grounding recommendations, refer to the National Electrical Code
published by the National Fire Protection Association.

For more information on terminal wiring and grounding applications, refer to publication

2711P-TD001

. You can find this publication in the Literature Library at

http://literature.rockwellautomation.com

.

About the Product

The base configured unit of the PanelView Plus 400 and 600 terminals includes these
components:

Power supply, AC or DC

Display with keypad, touch screen, or keypad and touch screen

Processor and memory

RS-232 and USB ports only

or

RS-232, USB, and Ethernet ports with interface for communication module

The fixed configuration of the PanelView Plus Compact 400 and 600 terminals includes these
components:

Power supply, DC

Display with keypad, touch screen, or keypad and touch screen

Processor and memory

RS-232, USB, and Ethernet ports without interface for communication module