Check the display, Startup information messages – Rockwell Automation 2711PC-x6xxxx PanelView Plus 400 and 600 Terminals Installation Instructions User Manual

Page 23

Advertising
background image

PanelView Plus and PanelView Plus Compact 400 and 600 Terminals 23

Publication 2711P-IN002G-EN-P - November 2009

Check the Display

If the terminal display is dim or unreadable:

check the brightness setting. From terminal Configuration mode, choose Terminal
Settings>Display Intensity.

check the contrast setting. From terminal Configuration mode, choose Terminal
Settings>Display Contrast.

check the Screen Saver settings. The backlight may turn off or dim the display
unexpectedly. From terminal Configuration mode, choose Terminal
Settings>Display>Screen Saver.

Startup Information Messages

Startup information messages display in a specific sequence on the terminal screen during
startup and typically display for a few seconds. These messages do not require that you
perform any action.

Message #

Message

Description

30

Watchdog Test

Tests the watchdog circuitry to verify system integrity.

1

RAM Test

Tests the RAM memory.

2

Image Search

Checks for new OS firmware upgrade on the external compact flash
card and the serial port.

11

Downloading Image

Transfers a new OS firmware upgrade to internal RAM. Message may
remain on screen for several minutes.

20

Transfer Image

Programs the OS firmware just downloaded into RAM. Message may
remain on screen for several minutes.

24

CRC Check

Checks the integrity of the OS firmware.

27

Decompress System

Decompresses the compressed OS firmware into RAM.

28

Starting System

Launches the operating system (OS).

29

System Check ###

Internal file system integrity check (### is percent progress indicator).

29.1

System Check

Internal file system check disabled. Contact technical support.

Advertising