4 PanelView Plus and PanelView Plus Compact 400 and 600 Terminals

Publication 2711P-IN002G-EN-P - November 2009

Hazardous Locations

This equipment is suitable for these locations:

Class I, Division 2 Groups A, B, C, D

Class II, Division 2 Groups F, G

Class III

Ordinary non-hazardous locations only

The following statement applies to use in hazardous locations.

The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum
ambient temperature. Do not install the terminals in environments where atmospheric gases
have ignition temperatures

less than 135 °C (275 °F).

WARNING

Explosion Hazard

Substitution of components may impair suitability for hazardous locations.

Do not disconnect equipment unless power has been switched off and area is
known to be non-hazardous.

Do not connect or disconnect components unless power has been switched off.

All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section
18-1J2 as appropriate.

Peripheral equipment must be suitable for the location in which it is used.