Protective earth connection, Ac power connections – Rockwell Automation 2711PC-x6xxxx PanelView Plus 400 and 600 Terminals Installation Instructions User Manual

Page 19

Advertising
background image

PanelView Plus and PanelView Plus Compact 400 and 600 Terminals 19

Publication 2711P-IN002G-EN-P - November 2009

AC Power Connections

The 400 to 600 terminals with an integrated AC power supply have these power ratings:

85…264V AC (47…63 Hz)

60V A maximum

The input power terminal block is removable and supports these wire sizes.

Protective Earth Connection

PanelView Plus AC terminals have a protective earth ground terminal that you must connect
to a low-impedance earth ground.

The terminals have the protective earth ground connection on the power input terminal
block. The protective earth terminal wiring requires a minimum wire gauge.

Wire Specifications for AC Input Power Terminal Block

Wire Type

Dual-wire Gauge

(1)

(1)

Two-wire max. per terminal.

Single-wire Gauge

Terminal Screw
Torque

Stranded or solid

Cu 90 °C (194 °F)

0.33…1.31 mm

2

22…16 AWG

0.33…2.08 mm

2

22…14 AWG

0.45 …0.56 N•m

(4…5 lb•in)

ATTENTION

The protective earth connection is required for both electrical safety and Electromagnetic
Compliance (EMC) with the EU (European Union) EMC directive for CE-mark conformance.

Protective Earth Wire Specifications for AC Power

Wire Type

Wire Gauge

Terminal Screw Torque

Stranded or solid

Cu 90 °C (194 °F)

2.08…3.31 mm

2

(14…12 AWG)

0.45…0.56 N•m (4…5 lb•in)