Environment and Enclosure
ControlNet Communication Ports
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in 
overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m 
(6561 ft) without derating.
The terminals are intended for use with programmable logic controllers. Terminals that 
are AC powered must also be connected to the secondary of an isolating transformer.
This equipment is considered Group 1, Class A industrial equipment according to 
IEC/CISPR 11. Without appropriate precautions, there may be potential difficulties 
ensuring electromagnetic compatibility in other environments due to conducted as well 
as radiated disturbance.
Korean Radio Wave Suitability Registration - This equipment is registered for 
Electromagnetic Conformity Registration as business equipment (A), not home 
equipment. Sellers or users are required to take caution in this regard.
This equipment is supplied as open-type equipment. It must be mounted within an 
enclosure that is suitably designed for those specific environmental conditions that will 
be present and appropriately designed to prevent personal injury resulting from 
accessibility to live parts. The interior of the enclosure must be accessible only by the use 
of a tool. The terminals meet specified NEMA Type and IEC ratings only when mounted in 
a panel or enclosure with the equivalent rating. Subsequent sections of this publication 
may contain additional information regarding specific enclosure type ratings that are 
required to comply with certain product safety certifications.
In addition to this publication, see:
•
Industrial Automation Wiring and Grounding Guidelines, for additional installation 
requirements, publication 
•
NEMA Standards publication 250 and IEC publication 60529, as applicable, for 
explanations of the degrees of protection provided by different types of enclosure.
ATTENTION
PanelView Plus terminals with ControlNet communications ports include a Network 
Applications Port (NAP). This port is for temporarily connecting programming terminals
to devices on a ControlNet network, and are not intended for continuous operation.