Usb ports – Rockwell Automation 2711PC-x6xxxx PanelView Plus 400 and 600 Terminals Installation Instructions User Manual

Page 6

Advertising
background image

6 PanelView Plus and PanelView Plus Compact 400 and 600 Terminals

Publication 2711P-IN002G-EN-P - November 2009

USB Ports

The PanelView Plus and PanelView Plus Compact terminals contain a single, universal serial
bus (USB) port that comply with hazardous location environments. This section details the
field wiring compliance requirements and is provided in accordance with the National
Electrical Code, article 500.

400 and 600 Terminals Control Drawing

Selected nonincendive field wiring apparatus must have nonincendive circuit parameters
conforming with Table 2.

Table 1 - 400 and 600 USB Port Circuit Parameters

400 and 600
Terminals

V

oc

I

sc

C

a

L

a

Groups A and B

Groups C and D

Groups A and B

Groups C and D

Series A and B 5.25V DC

1.68 A

10 µF

10 µF

15 µH

15 µH

Series C or
later

5.25V DC

1.68 A

10 µF

10 µF

3.5 µH

15 µH

Table 2 - Required Circuit Parameters for the USB Peripheral Device

V

max

V

oc

I

max

I

sc

C

i

+ C

cable

C

a

L

i

+ L

cable

L

a

USB

Peripheral

Device

Nonincendive Field
Wiring Apparatus

USB Port

Nonincendive Field Wiring

Associated Nonincendive Field Wiring Apparatus

PanelView Plus 400/600 Host Product

Advertising