Rockwell Automation 2711PC-x6xxxx PanelView Plus 400 and 600 Terminals Installation Instructions User Manual

Page 22

Advertising
background image

22 PanelView Plus and PanelView Plus Compact 400 and 600 Terminals

Publication 2711P-IN002G-EN-P - November 2009

The table shows indicator states if the terminal powers on and stops during startup.

Indicator States If the Terminal Stops During Startup

Fault (Red)

Indicator

Comm (Green)

Indicator

Description

Blinking

(1)

(1)

Blinking red indicates a recoverable error.

Off

Last firmware download failed.

Reload firmware using Firmware Upgrade Wizard (FUW) utility.

Blinking

EBC boot loader firmware failed or is missing.

Reload firmware using Firmware Upgrade Wizard (FUW) utility.

On

Windows CE OS firmware failed or is missing.

Reload firmware using Firmware Upgrade Wizard (FUW) utility.

On

(2)

(2)

Solid red indicates a nonrecoverable or fatal error.

Off

Fatal hardware error occurred.

Replace the terminal.

Blinking

Fatal hardware error in display.

Replace the terminal.