Rockwell Automation 2500 SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers User Manual

Page 11

Advertising
background image

Rockwell Automation Publication 2500-IN005B-EN-P - April 2012

11

SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers

8. Move the flange handle from the Disconnected to the Test position.

a. Press and hold the black button on the front of the door.
b. Start moving the handle to the left while releasing the black button.
c. Move handle until it clicks into the Test position.

9. Move the flange handle from the Test to the Connected position.

a. Press and hold the black button on the front of the door.
b. Start moving the handle to the left while releasing black button.
c. Move handle until it clicks into the Connected position.

IMPORTANT

Listen for the handle to click into place. Then, verify that the handle is locked
into place by trying to move the handle back and forth.

IMPORTANT

Listen for the handle to click into place. Then, verify that the handle is locked
into place by trying to move the handle back and forth.

Control and Network connections: ON
Line and Load Power: OFF

Test

Turn Off

Circuit Breaker

Press

Black Button

Move Handle

Flange Handle in
the Test Position

Black Button

Flange Handle in the
Connected Position

Control and Network connections: ON
Line and Load Power: ON

Connected

Turn Off

Circuit Breaker

Press

Black Button

Move Handle

Black Button