Use these instructions to install SecureConnect™ units in CENTERLINE® 2500 
Low Voltage Motor Control Centers (MCCs).
For additional information on the CENTERLINE 2500 MCC, refer to the 
CENTERLINE 2500 Low Voltage Motor Control Centers Installation 
Instructions, publicat
.
Before You Begin
When installing arc-resistant units, you must make sure you are installing a unit 
that has the same arc-resistance rating as the section in which it is being installed. 
Units that are not rated for 300 ms arc duration must not be installed in a section 
that is rated for 300 ms arc duration. The arc-resistant rating will not apply if that 
is done.
Topic
Page
Safety Guidelines for Installing and Removing SecureConnect Units
Additional Resources
ATTENTION: All covers and doors must be in place before applying power to the 
MCC. If units are removed, they must be replaced with the appropriate items 
such as units, doors, and unit support pans.