SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers

a. Using a screwdriver, push in the latch and rotate 1/4 turn. See

page 5

for latch position details.

b. Open the unit door completely.

5. Unplug or remove door-mounted pilot devices.

6. Move the link arm up and to the left to remove the pin from the gear hole.

7. Push the lever to the right to unlock the unit from the unit support pan.

8. Slide the unit out of the column to remove the unit.

The unit can now be completely removed from the column.

9. Close the unit door and secure the door latches.

ATTENTION: If you do not replace the unit with another SecureConnect unit,
there will be an opening in the unit door for the flange handle. The arc-resistant
rating will not apply if there is an opening in the door.

Link Arm

Gear Hole

Link Arm Decal Detail

Press lever to the right.

Press

Before

Removing

Unit

Label Detail