Unit support pan – Rockwell Automation 2500 SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers User Manual
Page 6
 
6
Rockwell Automation Publication 2500-IN005B-EN-P - April 2012
SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers
Safety Guidelines for 
Installing and Removing 
SecureConnect Units
Units with door-mounted operator handles, switches and disconnects must be in 
the OFF/O position before units are inserted or removed.
Unit Support Pan
,
Open the unit door completely and verify that the unit support pan has been 
installed. 
The unit support pan is secured with two screws on the right side and one screw 
on the left side.
ATTENTION: De-energize, lock out, and tag out all sources of power to the MCC 
when installing or removing MCC units. If MCC units will be installed or removed 
with power applied to the main power bus, follow established electrical safety 
work practices. Refer to the publication, NFPA 70E: Standard for Electrical Safety 
in the Workplace, for further information.
WARNING: If power sources are connected to the motor control center, use 
extreme caution when inserting units. All busbars and the line sides of the 
inserted units are energized and contact with these parts can cause injury or 
death.
ATTENTION: To insure operator safety and prevent equipment damage, we 
recommend that two people install or remove units that are in the upper six 
modules or over 1600 mm above floor level.
IMPORTANT
The unit support pan below the unit compartment must be in place before 
installing the SecureConnect unit. 
Screw 
locations on 
right side
Screw location 
on left side
Front side of unit support pan