Bypass contactor closures, Synchronous transfer test: verify sync lead angle – Rockwell Automation 7000 PowerFlex Medium Voltage (B Frame) Commissioning - ForGe (PanelView 550) User Manual
Page 120

116
Rockwell Automation Publication 7000-IN006B-EN-P - May 2013
Chapter 5 Commissioning the Drive
Bypass Contactor Closures
Sample Waveforms
Ch1: Bypass Contactor Close Command (BPC output at ACB, J1-12 & 402)
Ch2: Actual Closure of Bypass Contactor (using 9V battery across contactor
vacuum bottles)
Figure 65 - Sample waveform: Bypass contactor closures
Synchronous Transfer Test: Verify Sync Lead Angle
While simulating a synchronous transfer to determine the best lead angle:
• ensure you have configured and armed the Diagnostic Trend.
• capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB
test point “Vuvs”.
• capture and trigger on falling edge of the DC Link current waveform at
ACB test point “Idc1”.
• label the waveforms as “Vuv”, “Vuvs” and “Idc1”.
• save the worksheet as “Drift @ 15 Degree Lead Angle”, for example.
Table 7 - Oscilloscope Settings
Oscilloscope
Time Base
Wave Form
Test-Point
Waveform
Label
Chan. 1
10ms/div.
DC Link Current
Idc1
Idc1
Chan. 2
Motor Voltage
Vuv
Vuv
Chan. 3
Bypass Line
Voltage
Vuvs
Vuvs