Live synchronous transfer – Rockwell Automation 7000 PowerFlex Medium Voltage (B Frame) Commissioning - ForGe (PanelView 550) User Manual
Page 121

Rockwell Automation Publication 7000-IN006B-EN-P - May 2013
117
Commissioning the Drive Chapter 5
Sample Waveforms
Synchronous Transfer Test to verify Sync Lead Angle (50Hz System); Ch1: Idc1
(yellow), Ch2: Vuv (blue), Ch3: Vuvs (red)
Figure 66 - Sample waveform: Synchronous transfer test
Live Synchronous Transfer
While performing a live synchronous transfer:
• capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB
test point “Vuvs”.
• capture and trigger on falling edge of the DC Link current waveform at
ACB test point “Idc1”.
• label the waveforms as “Vuv”, “Vuvs” and “Idc1”.
• save the worksheet as “Synch on Motor 01”, for example.
Table 8 - Oscilloscope Settings
Oscilloscope
Time Base
Wave Form
Test-Point
Waveform
Label
Chan. 1
10ms/div.
DC Link Current
Idc1
Idc1
Chan. 2
Motor Voltage
Vuv
Vuv
Chan. 3
Bypass Line
Voltage
Vuvs
Vuvs