Printing and Uploading Drive Data
Figure 82 - HyperTerminal —stop transfer
19. Close the HyperTerminal program and disconnect the laptop from the
drive.
Uploading Control Data
PF7000 drives with ForGe control have a specifically-allocated memory location
to capture and store critical data in the event of a fault condition, referred to as
"Control Data". There are 8 buffers that store data sequentially on a first-in first-
out basis, ensuring the data of the eight most-recent faults is always available for
analysis.
This section describes the process for retrieving and uploading Control Data.
For required components and cable diagrams, refer to
1. Connect your laptop to the drive using a 9-pin null-modem cable to a serial
data port ( J4) on teh DPM board.