Step 5.

Attach the pulsetach but leave the mechanical coupling

between the pulsetach and the motor or flowmeter

unconnected.
Fasten the field wires from the pulsetach to the cable

assembly's terminal strip. Typical field connections are

shown in figures 3.2 to 3.5.
Note that 5V openĆcollector inputs require 464 ohm, 1/2

watt pullĆup resistors while 12V openĆcollector inputs

require 1000 ohm, 1/2 watt pullĆup resistors. Also note

that the output openĆcollector transistors in the pulsetach

should have more than 12 mA of current driving

capability.
Use twistedĆpair wire, connected as shown, for the

cabling between the pulsetach and the terminal strip. If

you use wire with less than 2 twists per inch, it should be

shielded. Note that the shield should only be connected

at one end. Ground the cable shield on the module side.

The recommended twistedĆpair wire is Beldent 8761

cable or equivalent.
Cable length should not exceed 600 feet. Maximum

operating cable length for your installation is dependent

upon the type of cable you use and the way the

pulsetach is wired to the module.

Step 6.

Mount the pulsetach's external power supply. The

external power supply should be able to provide either 5 V

at 25 mA plus the pulsetach's power requirements or

12 V at 25 mA plus the pulsetach's power requirements.

Check the specifications of the pulsetach you will be

using.
Fasten the wires from the power supply to the pulsetach.

For best results, the power supply voltage should be

adjusted to provide the specified voltage at the pulsetach.