5Ć6

5.3.1

No Interrupts

If interrupts are never received and the timeout parameter in the

hardware EVENT statement in the task is disabled, the task will

never execute and there will be no error codes displayed on the

Processor module:
Step 1.

Verify that the application task is correct.
Verify that your interrupt response task is checking the

proper interrupt acknowledge bit to determine which bit

caused the interrupt. Confirm that when an interrupt is

located the interrupt acknowledge bit is being reset. If this

is not done, the interrupt will occur once and will not

occur again.

Step 2.

Verify that the inputs are wired correctly.
Confirm that all terminal strip connections are tight. Use

an oscilloscope and check the pulses coming from the

pulsetach. The duration of the pulse should be at least 8

microseconds. The square wave signals should be free of

electrical noise. If electrical noise is present, check the

ground connections and increase the signal's shielding

as necessary.
If external inputs are used, connect a voltmeter to the

proper points on the terminal strip and toggle each

external device. The voltmeter should alternate between 0

and maximum voltage. If this does not happen, there is a

problem with either the device or the wiring to the

terminal strip.

Step 3.

Verify that the input circuit on the module is working

correctly.
Remove power from the system. Disconnect the

mechanical coupling between the motor and the

pulsetach. Apply power to the rack and the pulsetach.
Move the pulsetach in both directions. The FORWARD

LED on the faceplate should turn on when the pulsetach

is rotated in the forward direction. The REVERSE LED

should turn on when the pulsetach is rotated in the

opposite direction.
If the pulsetach rotates in the wrong direction, the

pulsetach input wires must be switched. In a

singleĆended wiring configuration, swap the A and B

inputs. In a differential wiring configuration, swap the A

and not A inputs.
Remove power from the rack and the pulsetach.

ReĆconnect the coupling between the motor and the

pulsetach. ReĆapply power to the system.
If external inputs are used, toggle the input device and

verify that the appropriate LEDs on the module's

faceplate are also toggling. If they are not, the input

circuit on the module is not working properly.

Step 4.

Verify that the module can be accessed.
Connect an IBMĆcompatible personal computer to the

system and load the Programming Executive software.

Refer to the AutoMax Programming Executive instruction

manual for more information.