Appendix f, Continued) – Rockwell Automation 57C421B Pulsetach Input Module/DCS 5000/AutoMax User Manual
Page 63

FĆ3
Appendix F
(Continued)
Examples of Local I/O Definitions
The following statement assigns symbolic name COUNTS! to register 6 on the
input module located in slot 11:
1000
IODEF COUNTS![ SLOT=11, REGISTER=6]
The following statement assigns symbolic name UPDATE_TIME% to register 2 of
the input module located in slot 4:
1020
IODEF UPDATE_TIME%[ SLOT=4, REGISTER=2]
The following statement assigns symbolic name INPUT_PULSE_TYPE@ to bit 8
of register 6 on the input module located in slot 7:
2050
IODEF INPUT_PULSE_TYPE@[ SLOT=7, REGISTER=6, BIT=8]
Remote I/O Definition
This section describes how to configure the module when it is located in a rack
that is remote from the Processor that is referencing it. Refer to the following
figure. Note that interrupts cannot be used with the module in a remote rack.
Processor Module
Remote I/O Master
Drop 0
I/O Module
Remote I/O Slave
Drop 7
Master Rack
Remote I/O Slave
Drop 2
Remote I/O Slave
Drop 1
Module in a Remote Rack