FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 17

Publication

1797-5.5 - September 2011

1797-IE8H Input Map (Read Words)

Bit

Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Channel 0 Input Data

1

Channel 1 Input Data

2

Channel 2 Input Data

3

Channel 3 Input Data

4

Channel 4 Input Data

5

Channel 5 Input Data

6

Channel 6 Input Data

7

Channel 7 Input Data

8

OA

Ch7

OA

Ch6

OA

Ch5

OA

Ch4

OA

Ch3

OA

Ch2

OA

Ch1

OA

Ch0

UA

Ch7

UA

Ch6

UA

Ch5

UA

Ch4

UA

Ch3

UA

Ch2

UA

Ch1

UA

Ch0

9

RF

Ch7

RF

Ch6

RF

Ch5

RF

Ch4

RF

Ch3

RF

Ch2

RF

Ch1

RF

Ch0

LF

Ch7

LF

Ch6

LF

Ch5

LF

Ch4

LF

Ch3

LF

Ch2

LF

Ch1

LF

Ch0

10

Reserved

H
Rbd

Reserved

Diagnostic Status

11

H Rb

Ch7

H Rb

Ch6

H Rb

Ch5

H Rb

Ch4

H Rb

Ch3

H Rb

Ch2

H Rb

Ch1

H Rb

Ch0

H
Fail

Ch7

H
Fail

Ch6

H
Fail
Ch5

H
Fail

Ch4

H
Fail

Ch3

H
Fail

Ch2

H
Fail

Ch1

H
Fail

Ch0

12

H
Tmt

Ch7

H
Tmt

Ch6

H
Tmt

Ch5

H
Tmt

Ch4

H
Tmt

Ch3

H
Tmt

Ch2

H
Tmt

Ch1

H
Tmt

Ch0

H
Cm

Ch7

H
Cm

Ch6

H
Cm

Ch5

H
Cm

Ch4

H
Cm

Ch3

H
Cm

Ch2

H
Cm

Ch1

H
Cm

Ch0

Where: Ch = channel

OA = Over Alarm

UA = Under Alarm

RF = Remote Fault

LF = Local Fault

H Rbd = HART Rebuild

H Rb = HART Readback

H Fail = HART Failure

H Tmt = HART Transmitter

H Cm = HART Communication

Advertising