1797-ie8 and 1797-ie8nf output map (write words), 1797-ie8h output configuration map – Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual

Page 19

Advertising
background image

FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 19

Publication

1797-5.5 - September 2011

1797-IE8 and 1797-IE8NF Output Map (Write Words)

Bit

Word 15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved High and Low Error Level

0…3

u/d

0…3

Filter Cutoff

0…3

Data Format

0…3

Flt
Md

0…3

1

Sq Rt Th

High and Low Error Level

4…7

u/d

4…7

Filter Cutoff

4…7

Data Format

4…7

Flt
Md

4…7

2

CF

Module Command

Module Command Data

Where: u/d = Up/Down

Flt Md = Fault Module

Sq Rt Th = Square Root Threshold

CF = Command Flag

1797-IE8H Output Configuration Map

Bit

Word 15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved High and Low Error Level

0…3

u/d

0…3

Filter Cutoff

0…3

Data Format

0…3

Flt
Md

0…3

1

Sq Rt Th

High and Low Error Level

4…7

u/d

4…7

Filter Cutoff

4…7

Data Format

4…7

Flt
Md

4…7

Where: u/d = Up/Down

Flt Md = Fault Module

Sq Rt Th = Square Root Threshold