1797-ie8h ce, cenelec i/o entity parameters on, This f – Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual

Page 42

Advertising
background image

42 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules

Publication

1797-5.5 - September 2011

1797-IE8H CE, CENELEC I/O Entity Parameters

Source output plus measurement input (+ to -) for channels 0…7

(terminals: 0…2; 4…6; 8…10; 12…14; 17…19; 21…23; 25…27; 29…31)

1797-IE8 and 1797-IE8NF UL, C-UL I/O Entity Parameters

If this product has the UL/C-UL mark, it has been designed, evaluated,
tested, and certified to meet the following standards:

UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus
for Use in Class I, II, and III Division 1, Hazardous (Classified)
Locations

UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical
Equipment for Use in Hazardous (Classified) Locations

UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2
Hazardous (Classified) Locations

UL 61010, UL Standard for Safety Electrical Equipment For
Measurement, Control, and Laboratory Use; Part 1: General
Requirements

CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive
Equipment for Use in Hazardous Locations

CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in
Class I Hazardous Locations

If concentrated capacitance
and/or inductance are available,
use the following values.

Ex ia

IIB

320 nF

10 mH

IIC

60 nF

2 mH

Protection Allowed

Capacitance

Allowed
Inductance

U

o

= 24.4V

I

o

= 92.5 mA

P

o

= 565 mW

C

i

= Negligible

L

i

= Negligible

Ex ia

119 nF

4 mH

Advertising