46 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules

Publication

1797-5.5 - September 2011

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus. The internal capacitances of C

i

of the terminal base must be taken

into account to verify the intrinsic safety.

Simple apparatus is defined as a device which neither generates nor stores

more than 1.2V, 0.1 A, 20

μ

J, or 25 mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.

This module, 1797-IE8, must be used with terminal base 1797-TB3 or

1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46 to 49 shall not be

connected.

WARNING

: Substitution of components may impair intrinsic safety.

AVERTISSEMENT:

La substitution de composant peut compromettre la

securite intrinseque.

1797-IE8, 1797-IE8H, and 1797-IE8NF FM I/O Entity Parameters

If this product has the FM mark, it has been designed, evaluated, tested, and
certified to meet the following standards:

FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous
(Classified) Locations General Requirements

FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)
Locations

FM C1. No.3615:1989, Explosionproof Electrical Equipment General
Requirements

FM C1. No.3810:1989, 1995, Electrical and Electronic Test,
Measuring and Process Control Equipment

ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment