Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual

Page 47

Advertising
background image

FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 47

Publication

1797-5.5 - September 2011

Wiring Methods

Wiring method 1 - Each channel is wired separately.

Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).

FM I/O Entity Parameters for 1797-IE8 and 1797-IE8NF

FM I/O Entity Parameters for 1797-IE8H

Wiring
Method

Channel Terminals V

oc

(V)

I

sc

(mA)

V

max

(V)

I

max

(mA)

V

t

(V)

I

t

(mA)

Groups C

a

(

μ

F)

L

a

(mH)

1 and 2

Any one

channel

(for

example,

ch0)

0(+), 1(sig) 23.7 92.5 -

-

-

-

A, B, IIC 0.06

2.0

C, E, IIB 0.18

8.0

D, F, G,

IIA

0.48 16.0

1(sig), 2(-)

5

1.0 28.0 93.0 -

-

A, B, IIC 100 1000

C, E, IIB 300 1000

D, F, G,

IIA

800 1000

0(+), 1(sig),

2(-)

-

-

-

-

23.7 93.5 A, B, IIC 0.06

2.0

C, E, IIB 0.18

8.0

D, F, G,

IIA

0.48 16.0

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

max

(V)

I

max

(mA)

Groups

C

a

(

μ

F)

L

a

(mH)

1 and 2

Any one

channel

(for

example,

ch0)

0(+), 1(sig), 2(-) 24.4

92.5

-

-

A, B

0.119

4.0

C, E

0.35

12.0

D, F, G

0.95

32.0

1(sig), 2(-)

28

110

A, B

0.119

4.0

C, E

0.35

12.0

D, F, G

0.95

32.0

Advertising