Fault mode - write words 0 and 1, Data format - write words 0 and 1 – Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual

Page 22

Advertising
background image

22 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules

Publication

1797-5.5 - September 2011

Fault Mode - Write Words 0 and 1

Word 0 Bit 00

Fault enable for Channels 0...3

Word 1 Bit 00

Fault enable for Channels 4...7

Where: O = disable

1 = enable with wire-off overload

“Add-on” Filter Selections - Write Words 0 and 1 or

Filter Cutoff Selections

Word

Bits

Description

0

07

06

05

Channels 0...3

1

07

06

05

Channels 4...7

0

0

0

Hardware filtering only (default filtering)

0

0

1

40 Hz (25 ms)

0

1

0

20 Hz (50 ms)

0

1

1

10 Hz (100 ms)

1

0

0

4 Hz (250 ms)

1

0

1

2 Hz (500 ms)

1

1

0

1 Hz (1 s)

1

1

1

0.5 Hz (2 s)

Remote Transmitter Error Up/Down - Write Words 0 and 1

Word 0 Bit 08

Up/down for Channels 0...3

Word 1 Bit 08

Up/down for Channels 4...7

Where: O = up

1 = down

Data Format - Write Words 0 and 1

Word

Bits

Description

0

04

03

02

01

Channels 0...3

1

04

03

02

01

Channels 4...7

0

0

0

0

0…22 mA = 0...22,000 with error steps (default)

0

0

0

1

0…22 mA = 0…110%, with error steps

0

0

1

0

0…22 mA = 0…104.8%, square root, with error steps

Advertising