Hart input data, Cyclic hart input data – Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual

Page 30

Advertising
background image

30 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules

Publication

1797-5.5 - September 2011

Cyclic HART Input Data

The HART input data holds the primary variables for the "live" HART
device, and other information gathered during the normal HART scan.
Additional "documentary" data is available through the pass through message
interface in the device information tables. Pass through messages are defined
in detail in the User Manual.

IMPORTANT

The HART Input Data for a channel may be zeroes if HART communications is
disabled for that channel. For more information on disabling HART
communications, refer to the Disable HART communications and HART
Disable functions in the Configuration Map table.

HART Input Data

Word

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved

Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0

(HART Communications Status)

1

Reserved

2

Ch0 HART Field Device Status

Ch0 HART Comm Status

3

Reserved

Ch0 HART Loop Status

4

Ch0 HART Primary Value

(IEEE 754-1985 Single-Precision 32 bit floating point)

5

6

Ch0 HART Secondary Value

(IEEE 754-1985 Single-Precision 32 bit floating point)

7

8

Ch0 HART Tertiary Value

(IEEE 754-1985 Single-Precision 32 bit floating point)

9

10

Ch0 HART Fourth (Quaternary) Value

(IEEE 754-1985 Single-Precision 32 bit floating point)

11

12

Ch0 Secondary Value Units Code

Ch0 Primary Value Units Code

13

Ch0 Fourth Value Units Code

Ch0 Tertiary Value Units Code

14

Ch1 HART Field Device Status

Ch1 HART Communication Status

15

Reserved

Ch1 HART Loop Status

16

Ch1 HART Primary Value

17