44 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules

Publication

1797-5.5 - September 2011

Wiring Methods

Wiring method 1 - Each channel is wired separately.

Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

μ

F)

L

a

(mH)

1 and 2

Any one

channel,

for

example,

ch0

0(+), 1(sig)

23.7

92.5

-

-

A, B, IIC

0.06

2.0

C, E, IIB

0.18

8.0

D, F, G, IIA

0.48

16.0

1(sig), 2(-)

5

1.0

-

-

A, B, IIC

100

1000

C, E, IIB

300

1000

D, F, G, IIA

800

1000

0(+), 1(sig),

2(-)

-

-

23.7

93.5

A, B, IIC

0.06

2.0

C, E, IIB

0.18

8.0

D, F, G, IIA

0.48

16.0

FLEX Ex Analog
Input I/O Module

Indicators

Female Bus

Field Wiring

Terminal Base

Terminal Base
Key

Male Bus

Connection

Key Position for
Terminal Base

Insertion

42055