Rockwell Automation 9220-CC QUICK START CONTROLNET NTWK User Manual

Page 7

Advertising
background image

ControlNet Network Compliance Tool

7

Publication 9220-10.3 — September 1997

Using the Compliance Tool

Before running any of the compliance tests, install the compliance tool as
shown on page 5.

1. Connect the DUT to the ControlNet coax media.

2. Set the MAC ID of the Device Under Test (DUT) to 00.

3. Verify that the DUT does not communicate on the network.

4. Reset the MAC ID to a valid address.

After you complete these steps, the DUT should join the network
and the communication LEDs for the connected channel should
be solid green.

If you are running the

Then

ControlNet object test

attach a ControlNet device to the Network Access Port
(NAP) of the DUT. (Do not use an “auto-address”node.)

keeper object test

set the MAC ID of the DUT to 1

keeper stub test

set the MAC ID of the DUT to a value between 2 and 99

You can run a test either in script mode or in individual mode.

"

Advertising