Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 143

Programming Reference
4-61
The adjusted values may be in any order. The frequency will not be affected at normal
acceleration or deceleration but will be avoided at continuous output frequency.
.
The avoided frequency range is:
(Avoidance freq. midpoint ‘n’ - freq. band ‘n’/2) < range < (avoidance freq. midpoint ‘n’ + freq. band ‘n’/2)
where n = 1, 2, or 3.
H.010, H.012, H.014 Avoidance Frequency Midpoint 1, 2, and 3
This parameter
specifies the midpoint
of each avoidance
frequency band
selected in H.011,
H.013, and H.015.
Parameter Range:
0.0 to 200.0 Hz
Default Setting:
0.0
Parameter Type:
Tunable
Refer also to parameters:
H.009 Avoidance Frequency Enable
H.011, H.013, H.015 Avoidance Frequency Band 1,
2, and 3
H.011, H.013, and H.015 Avoidance Frequency Band 1, 2, and 3
This parameter
specifies the
avoidance frequency
band that will be
applied to each
avoidance frequency
midpoint selected in
H.010, H012, and
H.014.
Parameter Range:
0.2 to 10 Hz
Default Setting:
2.0
Parameter Type:
Tunable
Refer also to parameters:
H.009 Avoidance Frequency Enable
H.010, H.012, H.014 Avoidance Frequency Midpoint
1, 2, and 3