U.000 torque reference source – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual

Page 150

Advertising
background image

4-68

LiquiFlo AC Drive, Software Reference Version 6.4

4.6.4 Second Menu Vector Parameter Descriptions (U.000 to U.048)

If U.000 = 0, the drive will always regulate speed.

If U.000 > 0, the drive will regulate torque or speed. Torque or speed regulation is
selected by a terminal strip digital input (see the P.007 configuration) or the network
option board (depending on the control source).

If torque regulation is selected:

•

the Current Limit parameter (P.005) is not applied.

•

asserting the START input when JOG is selected will enable the torque regulator,
not the speed regulator (i.e., P.020, P.021, and P.022 are not used).

•

the stop type will always be coast-to-rest regardless of the value in P.025 (Stop
Type).

If U.000 = 1, the analog input conditioning (P.009 through P.011) does not apply. The
analog input in this case is converted every torque regulator scan (0.5 ms) for external
closed-loop control (e.g., positioning applications using the QUIQ module).

If U.000 = 3:

•

The FWD/REV input can be used to invert the selected speed reference when it is
used as the torque reference.

•

If the speed reference is used as the torque reference, the %torque is computed as:

Speed value x 150 = %torque reference
U.017 (Top Speed)

This assumes that P.028 = U.017.

U.000 Torque Reference Source

This parameter
specifies the source
for the torque
reference when
torque regulation is
selected.

Parameter Range:

0 = Speed loop output

1 = Terminal strip analog input

2 = Option port (network torque reference register)

*

3 = Selected speed reference

*

If the AutoMax Network option is used, see P.063.

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

P.007 Terminal Strip Digital Inputs Configure