Starting Up the Drive for Volts/Hertz Regulation
1-15
Step 5.12 Press the ▲
key to increase the motor nameplate amps, or the ▼ key to
decrease motor nameplate amps.
The adjustment range depends on the
drive rating. See Appendix C.
VALUE ENTERED:
Step 5.13 Press the ENTER key to save the changed value.
After pressing ENTER, the same
parameter is displayed. You can now
move to the next parameter.
Step 5.14 Press the ▲
key to display H.003, Torque Boost Voltage.
This parameter is required to offset the
voltage drop of the motor at low speeds
and produce constant torque. For
example, high friction loads may require
high starting torque.
Refer to figure 4.11 for more
information.
Step 5.15 Press the ENTER key.
The default setting is 0.5.