P.003, P.004 – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 17

Starting Up the Drive for Volts/Hertz Regulation
1-7
Step 3.11 Press the ENTER key to display the default setting of P.003.
This shows that the default setting for
Minimum Speed is 5.0 Hz.
Step 3.12 Press the ▲
key to increase minimum speed or the ▼ key to decrease
minimum speed.
The adjustment range is:
0.5 Hz to the value set for P.004
(Maximum Speed).
VALUE ENTERED:
Step 3.13 Press the ENTER key to save the changed value.
After pressing ENTER, the same
parameter number is displayed. You can
now go to the next parameter.
Step 3.14 Press the ▲
key to display P.004, Maximum Speed.
This parameter sets the maximum
speed in Hz.
In addition, the drive has overfrequency
protection by means of H.022. Refer to
the description of this parameter and be
sure to set it appropriate to your
application.
5.0
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
p.003
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
p.004
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC