Frame 14 Installation
11-25
Circuit Breaker DIP Switch Settings
The DIP switches on the circuit breakers are configured to the correct
settings at the factory. However, the settings detailed in
below
should be verified before charging the circuit breaker motor operators and
operating the drive.
Table 11.C Circuit Breaker DIP Switch Settings
Figure 11.12 Circuit Breaker DIP Switches Location
Voltage Class
Drive ND Cont.
Amp Rating
L
S/I
N
I1
t1
S/I
I3
t2
ON/OFF 50% / 100%
400/480V AC
1770
0.76
3 s
S
1.5
0.1 s
OFF
na
2150
0.92
3 s
S
1.5
0.1 s
OFF
na
600/690V AC
1500
0.88
3 s
S
1.0
0.1 s
OFF
na
1900
0.84
3 s
S
1.0
0.1 s
OFF
na
2250
0.96
3 s
S
1.5
0.1 s
OFF
na
OFF
DI
S
CHARGED
S
PRING
L
S
I
N
L
N
I1 =
In x (0.4+
t1
S
I
t2
I2=
In x
I
3
=