Control Wiring for PowerFlex 700S Drives with Phase II Control
4-9
Hard Enable Circuitry
The PowerFlex 700S provides a dedicated hardware enable input for
applications that require the drive to be disabled without software
interpretation.
Primary Encoder
Interface -
Supports 5V/12V DC
differential encoders with
internal power supply.
Used as primary closed
loop speed feedback,
Primary Encoder - Internal Supply
Using Encoder 0 as speed feedback:
•
Par 222 [Motor Fdkbk Sel] = 0 - “Encoder 0” (default)
•
Par 232 [Encoder0 PPR] = Pulses/Rev for installed
encoder
Primary Encoder - External Supply
Input/Output
Connection Example
A-
A
Encoder
13
14
15
16
17
18
19
20
21
22
23
24
B-
B
Z-
Z
-
+
Power +V
Common -V
Shield
A-
A
Encoder
13
14
15
16
17
18
19
20
21
22
23
24
B-
B
Z-
Z
-
+
Advertising