6-2
Frame 9 Installation
Minimum Mounting
Clearances
Operating Temperatures
Frame 9 drives require a minimum of 1300 m
3
/h (765 cfm) of cooling air.
400.0 mm
(15.75 in.)
80.0 mm
(3.2 in.)
50.0 mm
(1.97 in.)
350.0 mm
(13.8 in.)
400.0 mm
(15.75 in.)
350.0 mm
(13.8 in.)
50.0 mm
(1.97 in.)
Refer to
for detailed dimension information.
PowerFlex Drive
Voltage Class Amp Rating
Surrounding Air Temperature
Normal Duty
Heavy Duty
700H
All
All
0 to 40
°
C
(32 to 104
°
F)
0 to 50
°
C
(32 to 122
°
F)
700S
400/480V AC
(540/650V DC)
All
0 to 40
°
C
(32 to 104
°
F)
0 to 40
°
C
(32 to 104
°
F)
600/690V AC
(810/932V DC)
170
0 to 40
°
C
(32 to 104
°
F)
0 to 40
°
C
(32 to 104
°
F)
208
0 to 35
°
C
(32 to 95
°
F)
0 to 40
°
C
(32 to 104
°
F)
Advertising