Rockwell Automation 1768-CNxxx ControlNet Communication Modules User Manual

Page 16

Advertising
background image

16

Rockwell Automation Publication CNET-IN005C-EN-P - July 2014

Chapter 1

Install a 1756 ControlNet Communication Module

To connect the module to the network with a tap, perform this procedure.

1. Remove and save the dust caps from the ControlNet taps.

2. Connect the tap’s straight or right-angle connector to the module’s BNC

connector.

3. Apply power to the module and check the status indicators to determine

whether the power supply and module are operating properly.

For more information about status indicators, see

1756 ControlNet Status

Indicators on page 37

.

ATTENTION: Do not allow any metal portions of the tap to contact any
conductive material. If you disconnect the tap from the module, place
the dust cap back on the straight or right-angle connector to prevent
the connector from accidentally contacting a metallic grounded surface.

If your network supports

Then connect the tap’s connector

Nonredundant media
(all 1756-CN

x modules)

From trunkline A to channel A on the module.

Redundant media
(1756-CNBR, 1756-CN2R, 1756-CN2RXT,
and 1756-CN2RK modules)

From trunkline A to channel A on the 1756-CN2R module.
From trunkline B to channel B on the 1756-CN2R module.

IMPORTANT

To avoid accidentally reversing the tap connections, before making your
connection, check the tap drop cable for the label indicating the attached
segment. Accidental connection reversals produce incorrect status displays and
require troubleshooting.

Trunkline A

Trunkline B

1756-CN2 Trunkline A

1756-CN2R Trunklines A and B

Dust Cap

Dust Cap

32464

Nonredundant Media

Redundant Media

Tap

Tap

Tap

Network

Network