Network channel status indicators – Rockwell Automation 1768-CNxxx ControlNet Communication Modules User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication CNET-IN005C-EN-P - July 2014

Appendix A

1756 ControlNet Status Indicators

Network Channel Status Indicators

Table 2 - Network Channel Status Indicators A and B

Status

Description

Off

There is no power.

Steady red

Unit has faulted.
Cycle power or reset unit. If the fault persists, contact a Rockwell Automation representative or distributor.

Alternating red/green

A self-test is being conducted.

Alternating red/off

Node has been configured incorrectly.
Check network address and other ControlNet configuration parameters.

Table 3 - Network Channel Status Indicators A or B

Status

Description

Off

Channel has been disabled.
Program the network for redundant media, if required.

Steady green

This is normal operation.

Flashing green/off

Temporary errors exist. The unit will self-correct.

Node is not configured to go online.
Make sure that the configuration manager node (keeper) is present and working and the selected address is not greater
than the maximum unscheduled node address (UMAX).

(1)

Flashing red/off

A media fault exists.
Check media for broken cables, loose connectors, or missing terminators.

No other nodes are present on the network.
Add other nodes to the network.

(1) The configuration manager node (keeper) is the node responsible for distributing ControlNet configuration data to all nodes on the network.