Chapter 3

Redundant Media

Figure 1 - Redundant Media Example

Observe these guidelines when planning a redundant media system in a
hazardous area:

Route trunk cables A and B differently to reduce the chance of both cables

being damaged simultaneously.

Trunk cables A and B may contain different lengths of cable if you are

using 1786-RPA/B repeater adapters. However, the difference in length
must not exceed 800 m (2640 ft).

Trunk cables A and B must have identical configurations. Each segment

must contain the same number of taps, nodes, and repeaters. Connect
nodes and repeaters in the same relative sequence on both trunk cables.

Each node on a redundant-cable link must support redundant coax

connections and be connected to both trunk cables at all times. Any nodes
connected to only one side of a redundant-cable link will result in media
errors on the unconnected trunk cable.

Install the cable system so that the trunk cables at any physical device

location can be easily identified and labeled with the appropriate icon or
letter. Each redundant ControlNet device is labeled so you can connect it
to the corresponding trunk cable.

Node

Trunk Cable A

Trunk Cable B

Node

Node

To use redundant media, all nodes must support redundant media.