Rockwell Automation 1768-CNxxx ControlNet Communication Modules User Manual

Page 41

Advertising
background image

Rockwell Automation Publication CNET-IN005C-EN-P - July 2014

41

1756 ControlNet Status Indicators

Appendix A

Any

Keeper: Unconfigured

The network configuration data maintained in memory by the keeper object has been erased or
corrupted.
Do any of the following:

Use RSNetWorx software to download or update the keeper object in the module.

Reset the module to the original factory settings, as described on

page 14

.

Keeper: Unconfigured (data format
changed)

The network configuration data maintained in memory by the keeper object is in a format
incompatible with the current revision of firmware.
Do any of the following:

Use RSNetWorx software to download or update the keeper object in the module.

Reset the module to the original factory settings, as described on

page 14

.

Keeper: Unconfigured (slot changed)

After the keeper object’s network-configuration data was downloaded, the module was moved to a
different spot in the rack.
Do any of the following:

Return the module to the proper slot.

Use RSNetWorx software to download or update the keeper object in the module.

Reset the module to the original factory settings, as described on

page 14

.

Keeper: Unconfigured (net address
changed)

The network address switches on the module have been changed since the keeper object’s
network-configuration data was downloaded.
Do any of the following:

Return the network address switches to their original setting.

Use RSNetWorx software to download or update the keeper object in the module.

Reset the module to the original factory settings, as described on

page 14

.

Keeper: Signature Mismatch

The network configuration data maintained in memory by the keeper object does not match the
current network configuration.
There is a valid active keeper on the network.
Do any of the following:

Use RSNetWorx software to download or update the keeper object in the module.

Reset the module to the original factory settings, as described on

page 14

.

Keeper: None Valid on Network

The network configuration data maintained in memory by the keeper object does not match the
current network configuration, and there is no valid active keeper on the network.
Use RSNetWorx software to download or update the keeper object in the module.
Important: The

Install the Module on page 14

procedure does not work. There is no valid active

keeper from which to crossload data.

(1) ControlLogix enhanced redundancy systems only.

Table 1 - OK Status Indicator and Display

Status

Display

Description