Rockwell Automation 1768-CNxxx ControlNet Communication Modules User Manual

Page 45

Advertising
background image

Rockwell Automation Publication CNET-IN005C-EN-P - July 2014

45

1756 ControlNet Status Indicators

Appendix A

Steady green or off

SO_1

(2)

Old primary switchover phase 1 is in progress.
If the display shows this message for more than 3 seconds, then the 1756-CNB/E module failed during transition from one
redundancy phase to another. Replace one or both redundancy modules.

SO_2

(2)

Old primary switchover phase 2 is in progress.
If the display shows this message for more than 3 seconds, then the 1756-CNB/E module failed during transition from one
redundancy phase to another. Replace one or both redundancy modules.

SO_3

(2)

Old primary switchover phase 3 is in progress.
If the display shows this message for more than 3 seconds, then the 1756-CNB/E module failed during transition from one
redundancy phase to another. Replace one or both redundancy modules.

SN_1

(2)

New primary switchover phase 1 is in progress.
If the display shows this message for more than 3 seconds, then the 1756-CNB/E module failed during transition from one
redundancy phase to another. Replace one or both redundancy modules.

SN_2

(2)

New primary switchover phase 2 is in progress.
If the display shows this message for more than 3 seconds, then the 1756-CNB/E module failed during transition from one
redundancy phase to another. Replace one or both redundancy modules.

SN_3

(2)

New primary switchover phase 3 is in progress.
If the display shows this message for more than 3 seconds, then the 1756-CNB/E module failed during transition from one
redundancy phase to another. Replace one or both redundancy modules.

?Cpt

(2)

The 1756-CNB/E module has not determined if it is compatible.
If the display shows this message for more than 3 seconds, then the 1756-CNB/E module failed during transition from one
redundancy phase to another. Replace one or both redundancy modules.

!Cpt

(2)

The 1756-CNB/E module has determined that it is not compatible.
Replace the 1756-CNB/E module with one of the correct type and revision.

(1) If switches are set to 00, the display scrolls ‘FAULT: ADDRESS SWITCHES = 00, ILLEGAL’. If switches are set to 99 in a redundant chassis pair, the display scrolls ‘FAULT: ADDRESS SWITCHES = 99, ILLEGAL IN

REDUNDANT SYSTEM’.

(2) ControlLogix redundancy systems only.

Table 4 - OK Status Indicator and Display (Continued)

Status

Display

Description

Advertising
This manual is related to the following products: