Redundant Media

These ControlNet bridge modules support redundant media:

1756-CN2R
1756-CN2RK
1756-CN2RXT
1756-CNBR/E
1768-CNBR

Use Redundant Media

You can run a second trunk cable between ControlNet nodes for redundant
media. With redundant media, nodes send signals on separate

trunks. The

receiving node compares the quality of the two signals and permits use of the
better signal while retaining the other signal on a back-up cable should the
primary trunk cable fail.

Trunk cables on a redundant cable link are defined by the segment number and
the redundant trunk-cable letter.

Actual ControlNet products are labeled with these icons:

The shaded icon represents redundant media.

In this example, the redundant trunk cable is trunk cable B.

Topic

Page

Use Redundant Media

33

IMPORTANT

ControlNet redundant media can tolerate only one fault. If there is a fault on
both channel A and B, network integrity is not guaranteed.