1768 ControlNet Module Status Indicators

OK Status Indicator and Display

Table 7 - OK Status Indicator and Display

Status Display

Description

Off

None

The module is not communicating due to a power supply fault or internal fault.
Do any of the following:

Check the power supply.

Check the cable connectors.

Make sure the module is firmly seated in the chassis.

Replace the module if the indicator remains off.

Steady red

Msg scrolls

The module’s network address is set to 00, an invalid ControlNet network address.
If switches are set to 00, the display scrolls FAULT: ADDRESS SWITCHES = 00, ILLEGAL.
Remove the module from the chassis, and set the network address to a valid value. For more information,
see

Install a 1768 ControlNet Communication Module on page 23

.

BPA# ERR

The module detected a different slot address from that latched in when you cycled power. Excessive noise
on the backplane causes this error.
Replace the chassis or module.

BPRX ERR

There are too many CRC errors being generated by the multicast backplane receiver, so the backplane
multicast receivers have been shut off.
Replace the module.

BPIC ERR

There is a hardware fault within the module.
Replace the module.

CNIC ERR

DUPL NODE

The module’s network address is the same as another module’s on the link.
Remove the module from the chassis, and set the network address to a unique value. For more
information, see

Install a 1768 ControlNet Communication Module on page 23

.

RACK ERR

The module cannot read backplane EEPROM, or the rack/slot address is incorrect.
Replace the chassis.

Flashing red

BOOT

The module has invalid firmware.
Update the module’s firmware with ControlFLASH software.

ROM UPDT

An update is in progress.

SNGL KPR!

The module detected that it has been connected to a ControlNet single-keeper network, version 1.5.
Update the module’s firmware at MAC ID 01 and reschedule the network.

Steady green

OK

Normal operation is occurring.

INIT

The module is initializing.

BW > MAX

The module is receiving too much network traffic and connections are timing out. The network
bandwidth has been exceeded.
If this happens frequently, add another 1768-CNB or 1768-CNBR module and split the traffic between
them.

SW ERR

The node address switch changed after cycling power.
We recommend that you either return switches to their original settings or replace the module as this
could indicate a hardware anomaly.

Flashing green

CNFG ERR

There is a ControlNet network configuration error.
Recheck the configuration.

NET ERR

There is a network cabling error or there are no other active nodes on the network.
Recheck your network cabling and make sure another node on the network is active (online).