Rockwell Automation SD3100 DISTRIB PWR SYS SD3100 DC PWR MODULE User Manual

Page 10

Advertising
background image

1-2

SD3100 Power Modules

Table 1.1 – SD3100 Drive Options

Drive Option

Code

Description

Control Power Source

1

1. User must select one option from this group.

6P

Standard capacity control transformer with primary fusing

6TB

115 VAC control power, factory wired from 115 VAC control bus to drive unit
(1250 and 1650A units only). Requires option CB90

6SC

115 VAC control power supplied by others

Dynamic Braking Contactor

2

2. This option includes a dynamic braking contactor mounted in a separate 20” MCC section.

14DB

Dynamic braking contactor option

Unit Door Nameplate

1

M3EW

White background with black lettering; phenolic label

Miscellaneous

14WLBL

Brady Datab™ wire labels

3

3. Cloth wire labels are standard. Datab labels provide a clear plastic cover on top of the labels for added protection.

J12

15 VDC, 15A duplex receptacle, user-wired

4

4. User must supply 115 VAC control power and wiring to the duplex receptacle.

J11

Audio phone jack

Auxiliary Contacts

989X

(2) normally open and (2) normally closed contactors mounted internally in
1250/1650A unit, or

(4) normally open and (4) normally closed contactors mounted internally in
3000A unit

Blower Starters

5, 6

5. User may select one option from this group.
6. Fuses and overload elements are user-supplied and must be power-matched to the installation.

14BN

(1) NEMA 1 FVNR starter assembly internally mounted with 30A fuse blocks

14B2N

(2) NEMA 1 FVNR starter assemblies internally mounted with 30A fuse
blocks

14B2NX

(2) NEMA 2 FVNR starter assemblies internally mounted with 60A fuse
blocks

14BI

(1) IEC 24A starter assembly internally mounted with 30A fuse blocks

14B2I

(2) IEC 24A starter assemblies internally mounted with 30A fuse blocks

14B2IX

(2) IEC 30A starter assemblies internally mounted with 60A fuse blocks

Protection

14LSP

Line RC suppressor module

7

7. Line RC suppressor is required for installations where the primary of the distribution transformer is 2300 VAC or greater.

14AFL

Air flow loss switches

Field Supply Upgrade

8, 9

8. Standard Field Power Module is rated to supply field currents up to 15A. The upgrade provides a Field Power Module rated up to 60A.

(Nominal field currents based on 85% efficiency, unit control power usage, and a 300V field supply.)

9. A separately-ordered, separately-mounted 7.5kVA to 25kVA field isolation transformer is required. See the following section.

14FX

Field supply upgrade for fields requiring 15 to 60A

Incoming Protection

1

CM

Circuit breaker

LF

Line fuses

Horizontal Power Bus

5

HB1600

1600A AC power bus for 1250A units with 460 or575 VAC inputs

HB2000

2000A AC power bus for 1250 and 1650A units with 460 or 575 VAC inputs

HB3000

3000A AC power bus for 1250 and 1650A units with 460 or 575 VAC inputs

Horizontal Control Bus

CB90

90A AC control bus for 1250 and 1650A units that have a horizontal power
bus option

Input Option

14HBC

AC power input is wired from the horizontal thru-bus to the circuit breaker/line
fuses for 1250 and 1650A units that have a horizontal power bus option