A.6 field power module specifications – Rockwell Automation SD3100 DISTRIB PWR SYS SD3100 DC PWR MODULE User Manual

Page 61

Advertising
background image

Technical Specifications

A-13

A.6 Field Power Module Specifications

Ambient Conditions

Storage temperature: -40 to 85° C (-40 to 185° F)

Operating temperature: 0 to 40° C (32 to 104° F)

Humidity: 5 to 95%, non-condensing

Altitude: Up to 1000 meters (3300 feet) without derating output power. For every
91.4 meters (300 feet) above 1000 meters, derate the output current 1%.

Enclosure

Enclosed chassis with all circuits covered and protected.

Cooling

Convection cooled.

Dimensions

Input Ratings

AC field input voltage: 230 to 460 VAC +/- 10%, continuous operation

AC line frequency: 48 to 62 Hz.

Source rating: 2 kVA to 30 kVA

Maximum short circuit current: 10kA

Internal field fuse rating:15A unit: 20A, 600V

60A unit: 90A, 700V

One minute overload: 150% of maximum current (once per hour)

Output Ratings

Additional Information

For additional information on DPS single-phase Field Power Modules, refer to
instruction manual S-3060.

Part Number

Height

Width

Depth

805405-3R

340 mm (13.4 in)

128 mm (5 in)

127 mm (5 in)

805405-5R

523 mm (20.6 in)

180 mm (7.1 in)

220 mm (8.7 in)

Part Number

AC Input

Maximum

Rated Power

Rated Current

@ 40º C

1

1. Maximum ambient temperature with a 15° C internal maximum temperature

(Minimum Field Power Module ambient: 55° C)

805405-3R (S2R)

460V

15kW

15A

805405-5R (S2R)

230V

12kW

60A

460V

24kW

60A

Advertising