Installation Guidelines

3-5

3.5

Wiring the Motor

To wire DC power to the motor, you will need to do the following:

select appropriate wires for the armature and field lines

connect the motor armature and motor field to the Power Module

Refer to your motor’s installation manual for additional information.

3.5.1 Selecting Wires for the Armature and Field Lines

Refer to table 3.3 for the wire to be used for armature connection and to table 3.4 for
the wire to be used for the field connection.

3.5.2 Connecting the Motor to the Power Module

To connect the motor to the Power Module perform the following steps:

Step 1. Connect the Power Module’s armature outputs, A1(+) and A2(-), to the

motor’s armature leads, A1 and A2. Refer to figure 2.5 (1250A units), figure
2.7 (1650A units), or figure 2.9 (3000A units).

Step 2. Connect the Field Power Module outputs, terminals 37 (+) and 35 (-), to the

motor’s field leads, F1 and F2. Refer to figure 3.2.

Note that for counter-clockwise rotation, connect output A1 to motor lead A1 and
output A2 to motor lead A2. Connect terminal 37 to lead F1 and terminal 35 to
lead F2.

For alternative wiring configurations, please check the motor’s installation manual.

!

ATTENTION: The user is responsible for conforming with all applicable
local, national, and international codes. Failure to observe this precaution
could result in damage to, or destruction of, the equipment.

Table 3.3 – Armature Wire Selection

DC Bus Current

(Amps)

Output Wires (AWG)

1250

5-500 kcmil

1650

6-500 kcmil

3000

10-500 kcmil

Table 3.4 – Field Wire Selection

Power Module Rating

Output Wires (AWG)

(15 Amp Field)

Output Wires (AWG)

(60 Amp Field)

1250A

10

#4

1650A

10

#4

3000A

10

#4