Determine network parameters, Chapter 3, Chapter – Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual

Page 17

Advertising
background image

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

17

Chapter

3

Configure an EtherNet/IP Communication
Module to Operate on the Network

This chapter describes how to configure an EtherNet/IP communication module
to operate on an EtherNet/IP network.

Determine Network
Parameters

To operate an EtherNet/IP network, you must define these parameters.

Topic

Page

Determine Network Parameters

17

Set the Network IP Address on a Module

18

Duplicate IP Address Detection

29

IP Address Swapping

30

DNS Addressing

31

Use EtherNet/IP Communication Modules in a Logix5000 Controller Application

32

EtherNet/IP Network Parameter

Description

IP address

The IP address uniquely identifies the module. The IP address is in the form xxx.xxx.xxx.xxx where each xxx is a number

from 000…254.

There are some reserved values that you cannot use as the first octet in the address. These numbers are examples

of values you cannot use:

001.xxx.xxx.xxx

127.xxx.xxx.xxx

223 to 255.xxx.xxx.xxx

The specific reserved values that cannot be used vary according the conditions of each application. The previous values

are only examples of reserved values.

Subnet mask

Subnet addressing is an extension of the IP address scheme that allows a site to use a single network ID for multiple
physical networks. Routing outside of the site continues by dividing the IP address into a net ID and a host ID via the
class. Inside a site, the subnet mask is used to redivide the IP address into a custom network ID portion and host ID
portion. This field is set to 0.0.0.0 by default.
If you change the subnet mask of an already-configured module, you must cycle power to the module for the change
to take effect.

Gateway

A gateway connects individual physical networks into a system of networks. When a node needs to communicate with
a node on another network, a gateway transfers the data between the two networks. This field is set to 0.0.0.0 by
default.

Advertising