Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 3 Configure an EtherNet/IP Communication Module to Operate on the Network

Set the Network IP Address with the Rotary Switches

This graphic shows the rotary switches on a 1756 EtherNet/IP communication
module. The location of the switches is dependant on the module.

At powerup, the module reads the rotary switches to determine if they are set to a
valid number for the last portion of the IP address. Valid numbers range from
001…254.

If the settings are a valid number, these conditions result:

IP address = 192.168.1.

xxx (where xxx represents the switch settings)

Subnet mask = 255.255.255.0

Gateway address = 0.0.0.0

The module does not have a host name assigned, nor does it use any

Domain Name System

We recommend that you set the rotary switches to a valid number before
installing the module.

If either of these conditions exist, the module attempts to use the BOOTP/
DHCP server to set the IP address:

Rotary switches are not set to a valid number
Module does not have rotary switches

For more information on using the BOOTP/DHCP server to set the IP address,
see

page 21

.

TIP

Some modules now provide a gateway address of 192.168.1.1 when the
network address is set with rotary switches. Refer to the product
documentation to determine the correct gateway address the module uses.

Advertising