Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

55

Control I/O Chapter 5

Rack-optimized Connections for I/O Modules

In this example, assume that each digital I/O module is configured for a rack-
optimized connection to the controller. Analog modules must be configured for
direct connections.

The rack-optimized connection conserves connections, but can limit the status
and diagnostic information that is available from the I/O modules.

To optimize the number of available connections, use a rack-optimized
connection between any digital I/O that allows it and the remote adapter that
connects the distributed I/O to the controller via the communication module.

Logix5575

EtherNet/IP

ControlNet

OK

FORCE SD

RUN

RUN

REM PROG

1 2

LNK1 LNK2 OK

10/100 BASE T

EtherNet/IP

1 2

LNK1 LNK2 OK

10/100 BASE T

EtherNet/IP

1 2

LNK1 LNK2 OK

10/100 BASE T

DC OUTPUT

ST
AT
ST
AT

Diagnostic

DC OUTPUT

ST
AT
ST
AT

Diagnostic

DC OUTPUT

ST
AT
ST
AT

Diagnostic

EtherNet/IP Network

Controller with EtherNet/IP
Communication Module

EtherNet/IP Adapters with I/
O Modules

Two Digital I/O Modules

Three Analog I/O Modules

Four Digital I/O
Modules

Switch

Example - System Connections

System Connections

Amount

Controller to local EtherNet/IP communication module

0

Controller to EtherNet/IP adapter with digital modules

(rack-optimized connection to each adapter)

2

Controller to EtherNet/IP adapter with analog modules

(direct connection for each analog I/O module)

3

Total connections used

5