Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual
Page 94

94
Rockwell Automation Publication ENET-UM001L-EN-P - March 2014
Chapter 7 Send Email
Configure the MSG Instruction That Contains the Email Text
To configure the MSG instruction that contains the email text, perform this
procedure.
1. Click the Configuration tab.
The Source Length is the number of characters in the email tag plus 4
characters.
In this example, the email text contains 65 characters.
2. Configure the MSG parameters for sending an email.
• From the Service Type pull-down menu, choose Custom.
• In the Service Code field, type 4b.
• In the Instance field, type 1.
• In the Class field, type 32f.
• In the Attribute field, type 0.
• From the Source Element pull-down menu, choose the tag that contains
your email text.
• In the Source Length field, type the number of characters in the email
plus four.
In this example, you would enter 65 for the number of characters plus 4
for a total of 69.
• From the Destination pull-down menu, choose a tag to contain the
status of your email transmission.
- 1734-AENT EtherNet/IP Network Configuration User Manual 22-COMM-E EtherNet/IP Network Configuration User Manual 20-COMM-E EtherNet/IP Network Configuration User Manual 1794-AENT EtherNet/IP Network Configuration User Manual 1783-Etxx EtherNet/IP Network Configuration User Manual 1769-Lxxx EtherNet/IP Network Configuration User Manual 1756-Enxx EtherNet/IP Network Configuration User Manual