Field termination unit (ftu), Field interface unit (fiu), Figure 2 functional block diagram – Rockwell Automation T8444 Trusted TMR Pulse Generator and Monitoring Module User Manual

Page 10: Trusted, Module t8444

Advertising
background image

Trusted

TM

Module T8444

Issue 09 Apr 10

PD-T8444

10

Fig 2 shows a simplified block diagram of the Trusted

TM

PG/M Module.

Figure 2 Functional Block Diagram

1.1. Field Termination Unit (FTU)

The Field Termination Unit (FTU) is the section of the I/O module that connects all three FIUs to a
single field interface. The FTU provides the Group Fail-safe switches and passive components
necessary for signal conditioning, over-voltage protection, and EMI/RFI filtering. When installed in a
Trusted

TM

Controller or Expander Chassis, the FTU field connector interconnects to the Field I/O Cable

Assembly attached at the rear of the chassis.
The SmartSlot link is passed from the HIU to the field connections via the FTU. These signals go
directly to the field connector and maintain isolation from the I/O signals on the FTU. The SmartSlot
link is the intelligent connection between active and standby modules for co-ordination during module
replacement.

1.2. Field Interface Unit (FIU)

The Field Interface Unit (FIU) is the section of the module that contains the specific circuits necessary
to interface to the particular types of field I/O signals. Each module has three FIUs, one per slice. For
the TMR Pulse Generator and Monitoring Module, the FIU contains one stage of the output switch
structure, and A/D monitoring circuits for each of the channels. Two additional A/D circuits provide
optional monitoring of the external field I/O supply voltage.
The FIU receives isolated power from the HIU for logic. The FIU provides additional power conditioning
for the operational voltages required by the FIU circuitry. An isolated serial link connects each FIU to
one of the HIU slices.
The FIU also measures a range of on-board “house-keeping” signals that assist in monitoring the
performance and operating conditions of the module. These signals include power supply voltages,
current consumption, on-board reference voltages, board temperature, and condensation

Advertising